NFPA 96 Regulations for Mobile Cooking Operations in Food Trucks

The NFPA 96 standard outlines specific regulations for mobile cooking operations, such as food trucks, to ensure safety and fire protection. The suppression systems in mobile cooking operations need to be inspected every 6 months. Here are the key requirements:



img

Hood and Ventilation Systems

  • 1. Installation:
  •      • Mobile cooking operations must have a properly installed hood and ventilation system designed to capture grease-laden vapors and exhaust them safely out of the vehicle.
  •      • At least one listed audible and visual notification appliance shall be installed on the exterior surface of the vehicle readily audible and visible to the public.
  •      • All mobile and temporary cooking operations that have a propane appliance and an electrical system must be equipped with a listed propane detector.
  • 2. Materials:
  •      • The hood and duct systems must be constructed of stainless steel or other non-combustible materials.
  • 3. Cleaning:
  •      • Regular cleaning of the hood and duct system is required to prevent grease buildup, which can be a significant fire hazard.

Fire Suppression Systems

  • 1. Requirement:
  •      • All mobile cooking operations must be equipped with an automatic fire-extinguishing system that meets the requirements of NFPA 17A (Standard for Wet Chemical Extinguishing Systems).
  • 2. Activation:
  •      • The fire suppression system should have both automatic and manual activation capabilities.
  • 3. Maintenance:
  •      • Regular maintenance and inspection of the fire suppression system are required to ensure it remains operational.

Fuel and Power Safety

  • 1. Fuel Shutoff:
  •      • There must be a means to automatically shut off the fuel supply (gas or electric) when the fire suppression system is activated.
  • 2. Fuel Storage:
  •      • Propane tanks and other fuel sources must be securely mounted and protected from potential impact or tampering.
  • 3. Electrical Safety:
  •      • Electrical systems must be installed according to applicable codes and regularly inspected for potential hazards.

Additional Safety Measures

  • 1. Portable Fire Extinguishers:
  •      • Food trucks must carry portable fire extinguishers, with at least one Class K extinguisher for cooking operations involving grease or oils.
  • 2. Training:
  •      • Operators and staff must be trained in the proper use of fire extinguishers and the manual activation of the fire suppression system.
  • 3. Ventilation:
  •      • Ensure adequate ventilation to prevent the accumulation of carbon monoxide and other harmful gases inside the vehicle.
  •      • All trucks/trailers utilizing nonelectric and open flames, must have at least one listed carbon monoxide detector.

By adhering to these NFPA 96 regulations, food truck operators can ensure a safer cooking environment and reduce the risk of fire-related incidents. Winninger Fire Protection provides expert consultation, design, and installation services to help you comply with these standards.